The Cathodic Protection transformer rectifiers “UKZT-TM” (UKZT-A OPE TM-GSM & UKZT-AU OPE TM-GSM) are intended for protection of underground metal constructions against soil corrosion by a method of cathodic polarization. In contrast to CPTR “UKZT-U”, this rectifiers have microprocessor controller “KATRON-SKZ” as control block. This makes possible integration of the rectifiers to the telemetry system “STEL-K” or to some others SCADA-systems by standard Modbus RTU protocol of CAN/RS485 interfaces with the ability to remotely monitoring and control of rectifiers settings. The controller “KATRON-SKZ” is realized as multi-blocks module and include microprocessor block, GSM-modem and reserve power supply block with external accumulator battery. This one give opportunity transfer measured values of rectifier’s output voltage and current, protective potential, alarm signals (as not sanctioned opening of a rectifier’s box), data of power counter and time counters by GSM communications.
The CPRT “UKZT-TM” have the universal construction, what make possible universal using of cathodic protection rectifiers of series “UKZT”, “UKZT-U” and brand name rectifiers “Don”, “Don-U” and “Don-TM” in the project phase and installation.
The CP transformer rectifiers “UKZT-TM” are made in two modifications:
UKZT-A OPE TM-GSM X,X Y1 – the automatic CP transformer rectifiers with manual and auto control of output current or protective potential. This one has dimentions of CP rectifiers of “UKZT” type.
UKZT-AU OPE TM-GSM X,X Y1 – the automatic CP transformer rectifiers with manual and auto control of output current or protective potential. This one has dimentions of CP rectifiers of “UKZT-U” type.
Measured and transferred data by controller:
– Value of output voltage
– Value of output current
– Value of protective potential (if reference electrode is connected)
– Values of time counters (time of work, and time of useful work)
– Values of power counter (as option)
– Values of main voltage AC (as option)
– Value of “pipe-anode” resistance
– Value of temperature inside the controller box
– Emergency signalisation to central computer and transfer dubler SMS-message to mobile phones of staff.
Archiving of electronic journal of the CP rectifier, with a measurement each hour and the volume of the journal for 2 last months (archive). Thanks to this option the controller has function of intelligent control in case of accident situation.
As example: Rectifier work in automatic mode with stabilization of protective potential. After some time a sensor of protective potential is destroyed and rectifier can not stabilize set value of protective potential. In this case, the controller send alarm message to central computer (staff cells) and after that read from archive the value of output current for value of protective potential which was set and switched to mode automatic stabilization of output current with set value which was read from archive.
CHARACTERISTICS
UKZT-A OPE TM-GSM 0,3 Y1 | UKZT-A OPE TM-GSM 0,6 Y1 | UKZT-A OPE TM-GSM 1,2 Y1 | UKZT-A OPE TM-GSM 2,0 Y1 | |||
UKZT-AU OPE TM-GSM 0,3 Y1 | UKZT-AU OPE TM-GSM 0,6 Y1 | UKZT-AU OPE TM-GSM 1,2 Y1 | UKZT-AU OPE TM-GSM 2,0 Y1 | UKZT-AU OPE TM-GSM 3,0 Y1 | UKZT-AU OPE TM-GSM 5,0 Y1 | |
Nominal output power, kWatt | 0,3 | 0,6 | 1,2 | 2,0 | 3,0 | 5,0 |
Nominal voltage of power suply by frequency 50 Hz ,V AC | 220+22 | |||||
Nominal output voltage, V DC: Regime 1 Regime 2 |
. 12 24 |
. 24 48 |
. 24 48 |
. 48 96 |
. 48 96 |
. 48 96 |
Nominal output current, A DC: Regime 1 Regime 2 |
25 12 |
25 12 |
50 25 |
42 21 |
64 32 |
100 50 |
The range of adjustment of output voltage, % |
5…100 |
|||||
Automatic stabilization of: output current, at the range, % protective potential, V |
5 — 100 |
|||||
Accuracy of automatic stabilization: output current, at the range, % protective potential, % |
+ 2,5 |
|||||
Efficiency, no less, % without filter FPP-1 with filter FPP-1 |
70 |
|||||
71 |
75 | 75 | 78 | 82 |
82 |
|
Pulsation of DC output voltage, no more, %: with filter FPP-1 without filter FPP-1 |
3 not normed |
|||||
Voltage overload protection activation, V |
390 |
|||||
Climatic modification, category of accommodation |
Y1 |
|||||
Safety class of service |
01 |
|||||
Protection against influence of an environment and contact with current carrying parts |
IP34 |
|||||
Data transfer protocol |
Modbus RTU (interfaces CAN/RS-485) |
|||||
The working range of temperature, C° |
-45 … +45 (max. +50) |
|||||
Mass, no more, kg |
45 (35) |
58 (48) | 62 (52) | 68 (58) | 75 |
90 |
Dimensions, mm ( WxHxL) |
460 х 855 х 400 (460 х 615 х 400 for UKZT-A OPE mod.) |